Black Start Unit
480 V • 60 Hz · LV black start unit
Select a procedure to run step-by-step.
Quick Reference
Rated Output480V / 60 Hz (verify nameplate)
Rated Speed1800 RPM (4-pole) / 3600 RPM (2-pole)
Oil Pressure (run)Normal range — verify nameplate / manual
Coolant Temp (run)Normal range — verify nameplate / manual
Fuel TypeDiesel — no water or contamination
Crank TimeoutPanel default ~10–15 sec cranking
Warm-Up Before Load2–3 minutes idle before closing breaker
Cool-Down Before Stop3–5 minutes unloaded before stopping
Alarm Reference
trip
LOW OIL PLow Oil PressureStop engine immediately — do not run without oil pressure.
trip
HI COOLANTHigh Coolant TempStop engine — check coolant level, thermostat, radiator.
trip
OVERCRANKFail to StartEngine failed to start. Check fuel, battery, starter motor.
trip
OVER VOLTOutput Over-VoltageOpen output breaker. Check AVR / voltage regulator.
warning
UNDER VOLTOutput Under-VoltageCheck load, AVR, governor settings. Do not close breaker.
warning
OVER FREQOver FrequencyCheck governor. Do not apply load until frequency stabilizes.
warning
UNDER FREQUnder FrequencyCheck governor setting and engine speed.
warning
BATT LOWLow Battery VoltageCheck battery charger, terminals, and battery condition.
trip
OVERLOADGenerator OverloadReduce load. Open non-critical breakers.
trip
E-STOPEmergency Stop ActiveReset only after identifying and correcting the root cause.