Back to 35 MW Package
Normal Shutdown
0%Normal shutdown & 4-hr lockout
Step 1 of 3
Initiate Normal Stop
Controlled shutdown from the HMI. Refer to OEM manual and site procedures.
HMI Reference

action
Gradually reduce load per site guidelines.
action
Confirm all personnel and downstream systems are aware.
action
Select STOP on the Turbine Start/Stop screen.
action
Verify 52G breaker opens. Ensure 480 V supply is NOT interrupted (must transfer within 20 sec or unit enters Emergency Stop).
0/4 items checked