Back to 34 MW Package

34 MW Emergency Stop

0%

Malfunction / emergency shutdown

Step 1 of 3

Step 1 – Malfunction Shutdown Recognition

If LV busbar loses voltage unexpectedly: M1 opens automatically and HMI shows voltage loss. Act immediately.

action

Check TCP HMI Alarm Summary — note first-out alarm and timestamp.

monitor

LV busbar lost voltage: 30s later M1 circuit breaker opens. HMI shows voltage loss.

action

Start the Black Start Diesel Genset (BSDG) from the HMI immediately.

monitor

Monitor BSDG voltage and speed. Close M2 when normal.

0/4 items checked