Step 1 – Malfunction Shutdown Recognition
If LV busbar loses voltage unexpectedly: M1 opens automatically and HMI shows voltage loss. Act immediately.
action
Check TCP HMI Alarm Summary — note first-out alarm and timestamp.
monitor
LV busbar lost voltage: 30s later M1 circuit breaker opens. HMI shows voltage loss.
action
Start the Black Start Diesel Genset (BSDG) from the HMI immediately.
monitor
Monitor BSDG voltage and speed. Close M2 when normal.