Back to 13 MW Package

SMT130 15kV Breaker

0%

Close/open 15kV breaker with auto-sync

Step 1 of 2

CLOSE – Connect 15kV breaker to bus

The 15 kV Circuit Breaker closes after confirming the generator is [Ready to Load] and bus conditions are compatible. Auto-sync checks frequency, voltage and phase.

monitor

Confirm [Ready to Load] in the TCP screen header.

monitor

On the ATS / switchgear panel: verify the 15 KV LOAD BREAK SWITCH is closed (RED ON).

monitor

Generator voltage: 13.8 kV ± 5% of the bus.

monitor

Frequency: 60 Hz ± 0.3 Hz.

monitor

If auto-sync is active: the system will close the 15 kV breaker automatically when conditions are met.

action

For manual closing: press the red 15 KV CIRCUIT BREAKER CLOSE/CLOSED pushbutton.

monitor

Verify the green OPEN/OPENED indicator turns off — breaker closed.

monitor

Monitor: generator load (kW) transfers to the bus with no overcurrent or reverse power alarms.

action

Adjust the kW setpoint as required (see 'Load Setpoint' procedure).

0/9 items checked