Back to 13 MW Package

SMT130 Emergency Stop

0%

Immediate shutdown – no cooldown

Step 1 of 3

Step 1 – Push Emergency Stop

Emergency stop does NOT include a cooldown period. Use only when there is an immediate threat to personnel or equipment.

Without NORMAL or EMERGENCY AC during an e-stop, start the off-skid diesel-generator IMMEDIATELY so the post-lube pump can run.

HMI Reference
action

Push the EMERGENCY STOP Switch (SB0472) on the unit control panel.

monitor

Generator unloads immediately.

monitor

ENGINE HOURS/START COUNTER (PC0470) stops logging.

monitor

After turbine coasts to stop and rundown timer expires, post-lubrication cycle begins automatically.

action

If NO EMERGENCY or NORMAL AC is available: start the off-skid diesel-generator IMMEDIATELY.

0/5 items checked