SMT130 Emergency Stop
0%Immediate shutdown – no cooldown
Step 1 of 3
Step 1 – Push Emergency Stop
Emergency stop does NOT include a cooldown period. Use only when there is an immediate threat to personnel or equipment.
Without NORMAL or EMERGENCY AC during an e-stop, start the off-skid diesel-generator IMMEDIATELY so the post-lube pump can run.
HMI Reference

action
Push the EMERGENCY STOP Switch (SB0472) on the unit control panel.
monitor
Generator unloads immediately.
monitor
ENGINE HOURS/START COUNTER (PC0470) stops logging.
monitor
After turbine coasts to stop and rundown timer expires, post-lubrication cycle begins automatically.
action
If NO EMERGENCY or NORMAL AC is available: start the off-skid diesel-generator IMMEDIATELY.
0/5 items checked