SMT130 Normal Stop
0%Cooldown shutdown & diesel handoff
Step 1 of 3
Step 1 – Restart Emergency Diesel (Single Unit)
For single-unit operation: EMERGENCY AC must be available BEFORE stopping. Failure to restart the diesel causes inadequate ventilation and post-lube failure.
Without EMERGENCY AC during shutdown, DC backup lube pumps will cycle on/off. AC post-lube (from diesel) is the preferred method.
action
At the off-skid emergency diesel-generator: start and close all circuit breakers to supply EMERGENCY AC.
monitor
On ATS panel: confirm WHITE EMERGENCY SOURCE AVAILABLE light is ON.
monitor
Confirm RED EMERGENCY CB CLOSE/CLOSED light is ON.
monitor
ATS will automatically transfer from NORMAL to EMERGENCY power source.
0/4 items checked