Back to 13 MW Package
SMT130 Pre-Start
0%Pre-start checks & AC power procedure
Step 1 of 3
Step 1 – Pre-Start Walk-Around
Contact maintenance and confirm all work permits are closed and no DANGER / DO NOT OPERATE tags are on any equipment before energizing.
HMI Reference

action
Walk around both frames (Turbine Frame and Generator Frame). Confirm all eight sections are accessible and closed.
action
Verify no maintenance tags on any equipment. Confirm all maintenance items are complete.
action
Confirm Turbine Exhaust preparation for operation is complete.
action
Confirm Fire Suppression System preparation for operation is complete.
action
Verify combustor and exhaust collector drain caps are open — required during operation.
action
Confirm TAI (Turbine Air Inlet) module is installed and secured.
monitor
No fuel leaks, oil leaks, or gas leaks at any connection point.
0/7 items checked