Back to 6.4 MW Package

SMT60 Gen Breaker

0%

Close/open GCB with auto-sync

Step 1 of 2

CLOSE – Connect GCB to bus

The GCB (Generator Circuit Breaker) closes when the turbine is in [Ready to Load]. In parallel/grid mode, auto-sync checks frequency, voltage and phase angle before closing.

monitor

Confirm [Ready to Load] in the TT4000 screen header.

monitor

Verify generator voltage is within the bus range (15 kV ± 5%).

monitor

Verify frequency: 60 Hz ± 0.3 Hz.

monitor

If automatic synchronizing is enabled: the system will wait for the sync window and close the GCB automatically.

monitor

If closing manually: wait for the synchroscope/indicator to confirm phase match.

action

On TT4000: press CLOSE GCB (or confirm the command in the TCP window).

monitor

Confirm the GCB is CLOSED — indicator on the HMI and switchgear shows closed.

monitor

Monitor: generator load (kW) ramps up smoothly. No overcurrent or reverse power trips.

action

Adjust load setpoint as needed (see 'Load Setpoint' procedure).

0/9 items checked