Back to 6.4 MW Package

SMT60 Emergency Stop

0%

Immediate shutdown – no cooldown

Step 1 of 2

Step 1 – Emergency Stop

Only use emergency stop when plant conditions require an IMMEDIATE shutdown. No cooldown period is included.

An emergency stop prevents turbine operation until acknowledged and reset via local ACKNOWLEDGE and RESET switches, and the backup relay system is reset. If no EMERGENCY AC power is available, start the off-skid diesel-generator immediately after the emergency stop.

action

Verify the off-skid emergency diesel-generator is running and EMERGENCY AC power is available.

monitor

EMERGENCY AC available — enclosure fans and AC post-lube pump can run.

action

Push the EMERGENCY STOP switch (SB0472).

monitor

Generator unloads immediately. ENGINE HOURS/START COUNTER stops logging.

0/4 items checked