Back to 6.4 MW Package
SMT60 Emergency Stop
0%Immediate shutdown – no cooldown
Step 1 of 2
Step 1 – Emergency Stop
Only use emergency stop when plant conditions require an IMMEDIATE shutdown. No cooldown period is included.
An emergency stop prevents turbine operation until acknowledged and reset via local ACKNOWLEDGE and RESET switches, and the backup relay system is reset. If no EMERGENCY AC power is available, start the off-skid diesel-generator immediately after the emergency stop.
action
Verify the off-skid emergency diesel-generator is running and EMERGENCY AC power is available.
monitor
EMERGENCY AC available — enclosure fans and AC post-lube pump can run.
action
Push the EMERGENCY STOP switch (SB0472).
monitor
Generator unloads immediately. ENGINE HOURS/START COUNTER stops logging.
0/4 items checked