Back to 6.4 MW Package

SMT60 Load Setpoint

0%

Load setpoint (kW limit)

Step 1 of 2

Load setpoint limit in kW

Load setpoint controls unit power output. Adjust from Setpoints screen on the control panel. Refer to OEM manual.

monitor

Confirm GCB is closed and the unit is generating load ([Running] state).

action

On TT4000 / control screen: navigate to GENERATOR or SETPOINTS screen.

monitor

Verify active control mode (kW Control, Speed Droop, etc.) in the "Speed/Load Control Mode" box.

action

Press the SETPOINTS button to open the setpoints window.

action

Locate the 'kW' or 'Load Setpoint' field. Tap the current value to edit.

action

Enter the desired load value in kW. MAX LIMIT: 6,400 kW (ISO) — do not exceed.

action

Press OK to confirm the new setpoint.

monitor

Verify the new value appears in the Setpoints window.

monitor

Monitor: generator load should move gradually toward the new setpoint.

action

Record the programmed setpoint, time of change and system condition (kV, Hz, temperature).

0/10 items checked