SMT60 Normal Stop
0%Cooldown & shutdown sequence
Step 1 of 3
Step 1 – Prepare EMERGENCY AC Power
For single-unit operation: the off-skid emergency diesel-generator MUST be running before you stop the SMT60.
Without EMERGENCY AC power during shutdown, the enclosure will not ventilate and the AC post-lube pump will not function. DC backup pumps will cycle — this is the less preferred method.
monitor
At the ATS/Switchgear panel, confirm green EMERGENCY CB OPEN/OPENED light is on.
action
Put the BLACK START/HAND/BLACK STOP selector switch into the BLACK STOP position.
action
At the off-skid emergency diesel-generator, start the diesel-generator and close all circuit breakers so EMERGENCY power is supplied.
monitor
White EMERGENCY SOURCE AVAILABLE light on; red EMERGENCY CB CLOSE/CLOSED light on; green NORMAL CB OPEN/OPENED light on.
0/4 items checked